Contactor, Size 00, 3-pole, AC-3 4 kW/400 V, flat connector terminal Auxiliary switch 01E (1 NC) 230 V AC 50 Hz, 277 V 60 Hz AC operation Snap-on mounting standard mounting rail 3TF20013AP0_datasheet_en
Standards
IEC/EN 609471,
IEC/EN 6094741,
IEC/EN 6094751 (auxiliary switches)
The SIRIUS 3RT12 and 3TF68/3TF69 vacuum contactors are suitable for use in any climate. They are finger-safe according to IEC 60529.
Terminal covers may have to be fitted onto the connecting bars, depending on the configuration with other devices. Terminal covers for 3RT12 and 3TF6 vacuum contactors, see “Accessories and Spare Parts” → “for SIRIUS 3RT12 and 3TF6 Vacuum Contactors”.
Connection method
The vacuum contactors are available with screw terminals (box terminals).
Contact reliability
If voltages ≤ 110 V and currents ≤ 100 mA are to be switched, the auxiliary contacts of the vacuum contactors or 3RH contactor relays should be used as they guarantee a high level of contact reliability.
These auxiliary contacts are especially suitable for solid-state circuits with currents ≥ 1 mA at a voltage of 17 V and higher.
Short-circuit protection
For short-circuit protection of the vacuum contactors with or without overload relays, refer to the Manuals and Configuration Manuals, see Technical specifications.
Electromagnetic compatibility (EMC)
The contactors with solid-state operating mechanism comply with the international standards IEC/EN 60947-1, IEC/EN 60947-4-1.
These contactors have been developed for environment A.
Note:
Environment A refers to private low-voltage or industrial networks/locations/plants, including high-grade sources of interference.
Environment A corresponds to devices of Class A with CISPR 11, EN 55011.
Note:
In connection with converters, the control cables must be routed separately from the load cables to the converter.
The standard contactors 3TF68 ..-.C.. and 3TF69 ..-.C.. for AC operation are fitted with an electronically controlled solenoid operating mechanism with a high interference immunity. The solenoid coil is connected to varistors for protection against overvoltages.
Electromagnetic compatibility
Contactor | Rated control supply voltage Us | Overvoltage type | Degree of severity | Overvoltage resistance |
---|---|---|---|---|
3TF6844-.C.., | 110 V … 132 V | Burst | 3 | 2 kV |
200 V … 277 V | Burst | 4 | 4 kV | |
380 V … 600 V | Burst | 4 | 4 kV |
Contactors 3TF68 ..-.Q.. and 3TF69 ..-.Q.. for AC operation are envisaged for operation in systems with AC control supply voltage that is particularly subject to strong interference. The solenoid systems of these contactors are configured in the DC economy circuit with rectification. The rectifier bridge is connected to varistors for protection against overvoltages.
Such interference can be caused, for example, by the following:
To reduce interference caused by frequency converters, the manufacturer recommends the provision of, for example, input filters, outputs filters, grounding or shielding in the plant.
Other measures that have to be taken for overvoltage damping:
If operating conditions are such that high levels of interference are created and no measures have been taken to reduce the interference injection into the control voltage level, use of the 3TF68..-.Q and 3TF69..-.Q contactors is especially recommended.
SMC Direct Operated 3 Port Solenoid Valve VX3x for Manifold Condition: New, Original or Alternate.
SMC Digital Vacuum Sensor ZSE20CF ZSE20C 3 Screen 2 Output + Analog IP65 Condition: New,…
SMC Direct Operated 3 Port Solenoid Valve VX3x for Manifold Condition: New, Original or Alternate.
SMC Flat Bracket Assembly ITV1000-2000-3000 Condition: New, Original or Alternate.
SMC Digital Vacuum Sensor ZSE20CF-L ZSE20CL 3 Screen IP65 with IO-Link Condition: New, Original or…
SMC Digital Vacuum Sensor ZSE20CF ZSE20C 3 Screen 2 Output + Analog IP65 Condition: New,…
This website uses cookies.