AS-i data decoupler 2 x 4 A Spring-type terminals, AS-i dual Data decoupling module IP20, SlimLine S22.5 spring-type terminals Overall width module 22.5 mm IN: 24 V / 30 V DC OUT: 2 x AS-i, 4 A Integrated overload protection Integrated ground fault detection Signaling contact Remote reset3RK19011DG221AA0_datasheet_en
With the aid of the S22.5 data decoupling module, the AS-Interface network can also be supplied with 24 V DC or 30 V DC from a standard power supply unit and the transmission of data and power can be realized along one cable.
The combination of data decoupling modules and standard power supply units is therefore a cost-efficient alternative to the service-proven AS-Interface power supply units.
The quality of the data signals and the reliable operation of the AS-i network are not negatively affected as the result.
The AS-Interface data decoupling module is designed for AS-Interface networks with 30 V or 24 V supply (AS-Interface Power24V).
Operation of an AS-i network with the data decoupling module and a 30 V standard power supply unit is technically equivalent to the use of an AS-Interface power supply unit and offers the service-proven features of AS-Interface for all applications.
AS?Interface Power24V uses a 24 V power supply unit in conjunction with a data decoupling module and is particularly suitable for
When using the double data decoupling module or other data decoupling modules, several AS?Interface networks can be operated with a single power supply unit. This generates another costs benefit.
Note:
The power supply units must comply with the PELV (Protective Extra Low Voltage) or SELV (Safety Extra Low Voltage) standards, have a residual ripple of < 250 mVpp, and in the event of a fault must limit the output voltage to a maximum of 40 V. SITOP power supplies (see “24 V power supply units” → “SITOP power supply”) or PSN130S 30 V power supply units (see “30 V power supply units”) are recommended.
Note on AS?i Power24V:
The length of an AS-i Power24V network is restricted to 50 m in order to limit the voltage drop along the cable.
AS?i masters, AS?i slaves and the sensors and actuators supplied through the AS?i cable must be designed for the reduced voltage. Sensors and actuators for the standard voltage range of 10 to 30 V can be supplied with sufficient voltage.
Please also continue to observe the requirements specified in the section entitled “Extension of AS?i Power24V” for implementation of AS?i Power24V, see “AS?Interface → Introduction → AS?Interface Specification → Extension of AS?i Power24V”.
SMC Direct Operated 3 Port Solenoid Valve VX3x for Manifold Condition: New, Original or Alternate.
SMC Digital Vacuum Sensor ZSE20CF ZSE20C 3 Screen 2 Output + Analog IP65 Condition: New,…
SMC Direct Operated 3 Port Solenoid Valve VX3x for Manifold Condition: New, Original or Alternate.
SMC Flat Bracket Assembly ITV1000-2000-3000 Condition: New, Original or Alternate.
SMC Digital Vacuum Sensor ZSE20CF-L ZSE20CL 3 Screen IP65 with IO-Link Condition: New, Original or…
SMC Digital Vacuum Sensor ZSE20CF ZSE20C 3 Screen 2 Output + Analog IP65 Condition: New,…
This website uses cookies.