Description
SIPLUS MM420 FS B 3 kW for medial exposure based on 6SE6420-2UD23-0BA1 6AG14202UD230BA1_datasheet_en
Technical specifications
Technical data | MICROMASTER 420 | |||
---|---|---|---|---|
Mains voltage and power ranges
|
200 V to 240 V 1 AC ±10 % | 0.12 kW to 3 kW | ||
200 V to 240 V 3 AC ±10 % | 0.12 kW to 5.5 kW | |||
380 V to 480 V 3 AC ±10 % | 0.37 kW to 11 kW | |||
Power frequency | 47 Hz to 63 Hz | |||
Output frequency | 0 … 650 Hz, (limitation to 550 Hz in production to comply with legal requirements) 1) | |||
Power factor | ≥ 0.95 | |||
Inverter efficiency | 96 % to 97 % | |||
Overload capability | Overload current 1.5 x rated output current (i.e. 150 % overload capability) for 60 s, cycle time 300 s | |||
Inrush current | Less than rated input current | |||
Control method | Linear V/f characteristic; quadratic V/f characteristic; multipoint characteristic (programmable V/f characteristic); flux current control (FCC) | |||
Pulse frequency
|
16 kHz (standard with 230 V 1/3 AC) 4 kHz (standard with 400 V 3 AC) 2 kHz to 16 kHz (in 2 kHz steps) |
|||
Fixed frequencies | 7, programmable | |||
Skip frequency ranges | 4, programmable | |||
Setpoint resolution
|
0.01 Hz digital 0.01 Hz serial 10 bit analog |
|||
Digital inputs | 3 fully programmable isolated digital inputs; switchable PNP/NPN | |||
Analog input | 1, for setpoint or PI controller (0 V to 10 V, scaleable or for use as 4th digital input) | |||
Relay outputs | 1, programmable, 30 V DC/5 A (resistive load); 250 V AC/2 A (inductive load) | |||
Analog output | 1, programmable (0 mA to 20 mA) | |||
Serial interfaces | RS-485, optional RS-232 | |||
Motor cable lengths | ||||
|
max. 50 m (shielded) max. 100 m (unshielded) |
|||
|
see variant dependent options | |||
Electromagnetic compatibility
|
Inverter available with internal EMC filter Class A; available as options are EMC filters to EN 55 011, Class A or Class B | |||
Braking | DC braking, compound braking | |||
Degree of protection | IP20 | |||
Operating temperature | –10 °C to +50 °C (+14 °F to +122 °F) | |||
Storage temperature | –40 °C to +70 °C (–40 °F to +158 °F) | |||
Relative humidity | 95 % (non-condensing) | |||
Installation altitude | Up to 1000 m above sea level without derating | |||
Standard SCCR (Short Circuit Current Rating) 2) |
100 kA | |||
Protection features for
|
Undervoltage | |||
Overvoltage | ||||
Overload | ||||
Earth faults | ||||
Short circuit | ||||
Stall prevention | ||||
Locked motor protection | ||||
Motor overtemperature | ||||
Inverter overtemperature | ||||
Parameter interlock | ||||
Compliance with standards | UL, cUL, CE, c-tick | |||
CE marking | Conformity with low-voltage directive 73/23/EEC | |||
Cooling-air volumetric flow required, dimensions and weights (without options)
|
Frame size (FS) | Cooling-air volumetric flow required (l/s)/(CFM) | H x W x D (mm)
|
Weight, approx. (kg) |
A | 4.8/10.2 | 173 x 73 x 149 | 1.0 | |
B | 24/51 | 202 x 149 x 172 | 3.3 | |
C | 54.9/116.3 | 245 x 185 x 195 | 5.0 | |
CFM: Cubic Feet per Minute |
|