Description
MICROMASTER 430 WITHOUT FILTER 3AC 380-480 V +10/-10% 47-63 HZ SQUARED TORQUE POWER 45 KW OVERLOAD 110% 60 S, 140% 3 S 650 X 275 X 245 (H X W X D) PROTECTION IP20 AMBIENT TEMP. -10 TO +40 DEG. C WITHOUT AOP/BOP 6SE6430-2UD34-5EA0_datasheet_en
Technical specifications
Technical data | MICROMASTER 430 | |||||
---|---|---|---|---|---|---|
Mains voltage and power ranges | 380 V to 480 V 3 AC ±10 % | 7.5 kW to 250 kW (variable torque) | ||||
Power frequency | 47 Hz to 63 Hz | |||||
Output frequency | for inverter 7.5 kW to 90 kW | 0 … 650 Hz, (limitation to 550 Hz in production to comply with legal requirements) 1) | ||||
for inverter 110 kW to 250 kW | 0 Hz to 267 Hz | |||||
Power factor | ≥ 0.95 | |||||
Inverter efficiency
|
for inverter 7.5 kW to 90 kW | 96 % to 97 % | ||||
for inverter 110 kW to 250 kW | 97 % to 98 % | |||||
Overload capability
|
for inverter 7.5 kW to 90 kW | Overload current 1.4 x rated output current (i.e. 140 % overload capability) for 3 s and 1.1 x rated output current (i.e. 110 % overload capability) for 60 s, cycle time 300 s | ||||
for inverter 110 kW to 250 kW | Overload current 1.5 x rated output current (i.e. 150 % overload capability) for 1 s and 1.1 x rated output current (i.e. 110 % overload capability) for 60 s, cycle time 300 s | |||||
Inrush current | less than rated input current | |||||
Control method | linear V/f characteristic; quadratic V/f characteristic; multipoint characteristic (programmable V/f characteristic); flux current control (FCC); energy saving mode | |||||
Pulse frequency | for inverter 7.5 kW to 90 kW | 4 kHz (standard) 2 kHz to 16 kHz (in 2-kHz-steps) |
||||
for inverter 110 kW to 250 kW | 2 kHz (standard) 2 kHz to 4 kHz (in 2-kHz-steps) |
|||||
Fixed frequencies | 15, programmable | |||||
Skip frequency ranges | 4, programmable | |||||
Setpoint resolution | 0.01 Hz digital 0.01 Hz serial 10 bit analog |
|||||
Digital inputs | 6 fully programmable isolated digital inputs; switchable PNP/NPN | |||||
Analog inputs | 2 programmable analog inputs
|
|||||
Relay outputs | 3, programmable 30 V DC/5 A (resistive load), 250 V AC/2 A (inductive load) |
|||||
Analog outputs | 2, programmable (0/4 mA to 20 mA) | |||||
Serial interfaces | RS-485, option RS-232 | |||||
Motor cable length | for inverter 7.5 kW to 90 kW | Without output choke | max. 50 m (shielded) max. 100 m (unshielded) |
|||
With output choke | See variant dependent options | |||||
for inverter 110 kW to 250 kW | Without output choke | max. 200 m (shielded) max. 300 m (unshielded) |
||||
With output choke | See variant dependent options | |||||
Electromagnetic compatibility
|
for inverter 7.5 kW to 90 kW | Inverter with internal filter Class A available | ||||
for inverter without filter | 7.5 kW to 15 kW | EMC filter Class B to EN 55 011 available as an option | ||||
18.5 kW to 90 kW | EMC filter Class B from Schaffner available as an option | |||||
110 kW to 250 kW | EMC filter Class A available as an option | |||||
Braking | DC braking, compound braking | |||||
Degree of protection | IP20 | |||||
Operating temperature range
|
for inverter 7.5 kW to 90 kW | -10 °C to +40 °C (+14 °F to +104 °F) | ||||
for inverter 110 kW to 250 kW | 0 °C to +40 °C (+32 °F to +104 °F) | |||||
Storage temperature | -40 °C to +70 °C (-40 °F to +158 °F) | |||||
Relative humidity | 95 % (non-condensing) | |||||
Installation altitude
|
for inverter 7.5 kW to 90 kW | up to 1000 m above sea level without derating | ||||
for inverter 110 kW to 250 kW | up to 2000 m above sea level without derating | |||||
Standard SCCR (Short Circuit Current Rating) 2) |
FSC: 100 kA FSD, FSE, FSF, FSFX, FSGX: 65 kA |
|||||
Protection features for | undervoltage, overvoltage, overload, earth faults, short-circuits, stall prevention, locked motor protection, motor overtemperature, inverter overtemperature, parameter change protection | |||||
Conformity with standards | for inverter 7.5 kW to 90 kW | UL, cUL, CE, c-tick | ||||
for inverter 110 kW to 250 kW | UL available soon, cUL available soon, CE | |||||
CE marking | Conformity with low-voltage directive 73/23/EEC | |||||
Cooling-air volumetric flow required, dimensions and weights (without options)
|
Frame size (FS) | Cooling-air volumetric flow required (l/s)/(CFM) | H x W x D (mm) | Weight, approx. (kg) | ||
C | 54.9/116.3 | 245 x 185 x 195 | 5.7 | |||
D | 2 x 54.9/2 x 116.3 | 520 x 275 x 245 | 17 | |||
E | 2 x 54.9/2 x 116.3 | 650 x 275 x 245 | 22 | |||
F without filter | 150/317.79 | 850 x 350 x 320 | 56 | |||
F with filter | 150/317.79 | 1150 x 350 x 320 | 75 | |||
FX | 225/478.13 | 1400 x 326 x 356 | 116 | |||
GX | 440/935 | 1533 x 326 x 545 | 174 | |||
CFM: Cubic Feet per Minute |
|