Description
SIMATIC S7-1200 PLC CPU S7-1215C DC DC Relay 6ES7215-1HG40-0XB0
Siemens SIMATIC S7-1200 PLC CPU S7-1215C compact CPU, The New Generation of classic S7-200 PLC.
6ES7 215-1HG40-0XB0 6ES7215-1HG40-0XB0 6ES72151HG400XB0
Model No.: S7-1200 S7-1215C PLC CPU 1215C Relay output
Power Supply: DC 20.4-28.8 V DC
Output Type: 10 Bits Relay outputs.
Digital Input: 14 Bits 24V DC Inputs.
Analog Input: 2 Channels Analog 0-10 V DC input.
Analog Output: 2 Channels Analog 0-20 mA DC output.
Storage: Program/data memory 125 KB
Communication Interface: 2 PROFINET ports
6ES72151HG400XB0_datasheet_enSiemens SIMATIC S7-1200 PLC Standard CPUs list
13 standard CPUs
Graded performance for a wide range of different applications
Features | CPU 1211C | CPU 1212C | CPU 1214C | CPU 1215C | CPU 1217C |
Versions | DC/DC/DC, AC/DC/relay, DC/DC/relay | ||||
Work memory, integrated | 50 KB | 75 KB | 100 KB | 125 KB | 150 KB |
Load memory, integrated | 1 MB | 2 MB | 4 MB | 4 MB | 4 MB |
Memory card | SIMATIC Memory Card (optional) | ||||
Digital inputs/outputs, integrated | 6/4 | 8/6 | 14/10 | 14/10 | 14/10 |
Analog inputs, integrated | 2 | 2 | 2 | 2 | 2 |
Analog outputs, integrated | 0 | 0 | 0 | 2 | 2 |
Process image | 1024 bytes for inputs, 1024 bytes for outputs | ||||
Expansion by signal board | Max. 1 | Max. 1 | Max. 1 | Max. 1 | Max. 1 |
Expansion by signal modules | No | Max. 2 | Max. 8 | Max. 8 | Max. 8 |
Expansion by communication modules | Max. 3 | Max. 3 | Max. 3 | Max. 3 | Max. 3 |
General technical specifications of S7-1200
Degree of protection | IP20 acc. to IEC 529 |
Ambient temperature | Operation (95% humidity) |
Horizontal installation | -20 … +60 °C |
Vertical installation | -20 … +50 °C |
Transportation and storage | -40 … +70 °C |
With 95% humidity | 25 … 55 °C |
Insulation | |
5/24 V DC circuits | 500 V AC test voltage |
115/230 V AC circuits to ground | 1500 V AC test voltage |
115/230 V AC circuits to 115/230 V AC circuits | 1500 V AC test voltage |
230 V AC circuits to 5/24 V DC circuits | 1500 V AC test voltage |
115 V AC circuits to 5/24 V DC circuits | 1500 V AC test voltage |
Electromagnetic compatibility | Requirements of the EMC directive |
Noise immunity acc. to | Test acc. to: |
EN 50082-2 | IEC 801-2, IEC 801-3, IEC 801-4, EN 50141, EN 50204, IEC 801-5, VDE 0160 |
Emitted interference acc. to EN 50081-1 and | Test according to |
EN 50081-2 | EN 55011, Class A, |
Group 1 | |
Mechanical strength — Vibrations, test acc. to / tested with | |
1 | IEC 68, Part 2-6: |
2 | 10 … 57 Hz; |
3 | constant amplitude |
4 | 0.3 mm; |
5 | 58 … 150 Hz; |
6 | constant acceleration 1 g (mounted on DIN rail) or |
7 | 2 g (mounted in switchboard); |
8 | mode of vibration: |
9 | frequency sweeps with a sweep rate of 1 octave/minute; |
10 | duration of vibration: |
11 | 10 frequency sweeps per axis in each direction of the three mutually perpendicular axes |
Mechanical strength — Shocks, test acc. to / tested with | |
1 | IEC 68, Part 2-27/half-sine: |
2 | magnitude of shock 15 g (peak value), duration 11 ms, 6 shocks in each of the three mutually perpendicular axes |